Appendix
A-7
A.2 Error code table
A.2.1 Error code for user defined communication
If error occurs in execution of function block with SND_MSG & RCV_MSG function block for user defined
communication, the error code is indicated on status output of function block. The following table is for error codes
occurred in execution of function
STATUS value
HEX Dec
Meaning
Action to take
H0E 14
Input to FNAM isn’t present or more than 16
figures
Verify input to FNAM.
H10 16
Position of Cnet I/F module is incorrectly
specified.
Enter SLOT_NO value correctly.
H11 17
Cnet I/F module isn’t applied to the slot
assigned to SLOT_NO, or is out of order.
Check operation status of Cnet I/F module of
assigned slot.
H12 18
Input parameter of function block is
incorrect (Ex.: CH, LEN1,…)
Check input parameter.
H14 20
Response frame not requested has been
received.
Verify receive frame of self station or transmission
frame of other station again.
H15 21
Response frame from Cnet I/F module has
not been received.(waiting time excceded)
Verify whether Cnet I/F module is user defined
communication mode.
H40 64
Operation of RS-232C/422 channel is not
RUN.
Perform operation RUN with frame editor..
( Menu: [ Online Run/Stop] )
H41 65
Frame names used in frame editor and in
communication command do not fit each
other.
Reconcile frame names in frame editor and frame
entered in FNAM.
H42 66
Frame name can not be found due to
abnormal CPU during operation. (during
transmission)
1) Download frame again.
2) Check if CPU is normal or not.
H43 67
Frame specified in FNAM has not been
received from other station.
1) Verify receive frame again.
2) Verify other station’s transmission frame again.
H44 68
Frame has not been downloaded from
frame editor.
Download frame.