A.1 LED indication specification
A.1.1 Applicable type
G3L-CUEA, G4L-CUEA, G6L-CUEB, G6L-CUEC, G7L-CUEB, G7L-CUEC
A.1.2 LED indication specification during normal operation
1) Operation status indication (when LED display switch not pushed)
[Table A.1] G3L-CUEA/G4L-CUEA
LED No.
Name
Normal LED status
Remark
0 RUN
On during RS-232C channel operation/
Flash in Flash Memory Write Mode
Ver.2.0
Flash Write Mode
Flash per cycle of 1sec
1
TX
On during transmission via RS-232C
Flash if in communication
2
RX
On during receive via RS-232C
Flash if in communication
3
ACK
On during ACK transmission/Off after NAK transmission
4
NAK
On during NAK transmission/Off after ACK transmission
5
ERR
Protocol error/On during SIO-error
Flash if in error
6
RS
- 232C
channel
MODEM
On during setting modem communication mode
7
SYS-RUN
On dimly during interfacing with CPU of PLC
8
RUN
On during setting channel to RS-422
9
TX
On during transmission via RS-422
Flash if in communication
10
RX
On during receive via RS-422
Flash if in communication
11
ACK
On during ACK transmission/Off after NAK transmission
12
NAK
On during NAK transmission/Off after ACK transmission
13
ERR
Protocol error/On during SIO-error
Flash if in error
14
RS - 422 channel
RS-485
On during RS-485 setting/Off during RS-422 setting
15
SYS-ERROR
Flash during serious error occurrence
H/W error
Remark
[Note1] It flashes if system H/W error or serious S/W error occurs, and the error status is indicated with upper 5 Bit
(LED ‘0’~‘4’). For the details, see ‘A.1.3 LED indication specification during abnormal operation’.