Chapter 4 Performance specification
4-25
[Table4.6] Checklist for module’s LED
LED type
If normal
If abnormal
Action to take
RUN ON OFF
1)
..
Run RS-232C channel operation using Frame Editor
TX
Flash if in
transmission
No flash
1)
Check cable connection between module and dedicated modem
2)
Check setting of mode program and station number based on
module operation mode
RX
Flash if in
receiving
No flash
1)
Check connection of dedicated line
2)
Check status of dedicated line
3)
Check cable connection between module and dedicated modem
4)
Check if data is transmitted from the other station’s dedicated
modem
ERROR OFF Flash
1)
Check if communication speeds of dedicated modem and
module are identical
2)
Check if data bit setting of dedicated modem is identical with
calculated basic-setting values of module
3)
Check connection of cable
MODEM ON
OFF
1)
Download communication type of RS-232C channel as set to
dedicated modem via Frame Editor
2)
Let channel operation mode set to stand-alone mode
4) LED display & Troubleshooting for dedicated modem: Since LED specification for dedicated modem differs
according to makers, user’s manual for modem shall be referred to. [Table4.5] describes how to troubleshoot in
dedicated modem based on common specification of LED display.
[Table4.7] Checklist for dedicated module’s LED
LED type
If normal
If abnormal
Action to take
TXD Flash OFF
1)
If module’s TX LED doesn’t flash, follow LED Checklist to
troubleshoot
2)
If module’s TX LED flashes, check cable connection
between module and dedicated modem