Chapter 7 Communication function
7-70
1
Monitor execution (Y##)
This is a function to execute the reading of variable registered by monitor registration This also specifies
registered No. and execute the reading of variable registered in that number.
1)
Request format(PC -> PLC)
Format
Name
Header
Station No.
Command
Registration No
Tail
Frame check
Frame(Ex.) ENQ
H10
Y(y)
H1F
EOT
BCC
ASCII
value
H05 H3130
H59(79)
H3146 H04
9
Registration No. is to be the same as the registered No. during monitor registration for monitor execution.
9
BCC : When command is one of lower case(y), only one lower byte of the value resulted by adding 1 byte
each to ASCII values from ENQ to EOT is converted into ASCII and added to BCC.
9
In computer request format, registration No. can be set to 00 ~ 31(H00 ~ H1F).
2)
Response format(for PLC of ACK response)
A) In case registration format of registration No. is the individual reading of direct variables
Format
Name
Header
Station
No.
Command
Registration
No
Number of
blocks
Number
of data
Data
Tail
Frame
check
Frame
(Ex.)
ACK H10 Y(y)
H1F
H01 H04 H9183AABB ETX BCC
ASCII value
H06
H3130
H59(79)
H313F
H3031
H3034
H393138334141
4242
H03
B) In case registration format of registration No. is the continuous reading of direct variables
Format
Name
Header
Station
No.
Command
Registration
No
Number of
data
Data
Tail
Frame
check
Frame (Ex.)
ACK
H10
Y(y)
H1F
H04
H9183AABB
ETX
BCC
ASCII value
H06
H3130
H59(79)
H313F
H3034
H3931383341414242
H03