Chapter 5 Frame Editor
5-14
[Figure 5.5] Example of BCC basic setting
Data Type : Set selecting type of BCC calculation result to ASCII or HEX in frame.
ASCII : Insert BCC calculation result as converted into ASCII data in BCC area with 2 byte of BCC
value available to be transmitted and received.
HEX. : Insert BCC calculation result as converted into HEX. data in BCC area with 1 byte of BCC value
available to be transmitted and received.
Check Rule : As of menu to set BCC calculation type, it can specify calculation types of Default, Sum,
Multiplication or Exclusive OR, and range. Regardless of calculation types, calculation is performed based on
ASCII code values if the frame is of ASCII, and based on frame HEX values if the frame is of HEX.
Example of BCC calculation according to BCC calculation type set is described below with ASCII
communication frame.
Frame type
Header
Frame body
Tail
Frame contents
STX
ENQ
0 0 R S B 2 0 0
EOT
BCC
ASCII code
H02 H05 H30
H30
H52
H53
H42
H32
H30 H30 H04
BCC calculation range
H[0] H[1] S[0]
S[1]
S[2]
S[3]
S[4]
S[5]
S[6] S[7] T[0]
As
set