Chapter 5 Frame Editor
5-19
[Figure 5.8] How to use immediate response
(a)
Immediate response if not selected: transmits response frame by PLC programming for
transmission.
(b)
Immediate response if selected: transmits applicable response frame immediately after received
by Cnet I/F module. (Programming in PLC is unnecessary)
If immediate response frame has been set, the same transmitted frame as the setting name shall be defined.
ARRAY data cannot be transmitted in the transmitted frame of immediate response.
D) Set received frame per segment. Setting is same as in transmitted frame, however such ARRAY variable
names in variable data area shall be surely used as RD1, RD2, RD3 and RD4. When PLC programming, data
entering variable data area is received in RD1~RD4 while RCV_MSG function block is being input. It means
that the data in setting area to RD1 array of Frame Editor among the received frames from the other station is
let saved in ARRAY variable set to RD1 of RCV_MSG function block in user program. If CONVERT is selected
in Frame Editor, ASCII data is saved as converted to figures, and as of characters as they are if NONE is
selected.
GLOFA PLC CPU
Cnet I/F module
Other’s
communication
device
RECEIVE
RECEIVE
REPLY
REPLY
GLOFA PLC CPU
Cnet I/F module
RECEIVE
RECEIVE
REPLY
Other’s
communication
device