Chapter 11 Troubleshooting
11-2
[Table 11.4] Error during TX monitor operation of frame editor
Error code
Error indication
Error contents
ERR-6
[No sent data] message occurs from the
beginning during requesting of TX moni-
tor start
Incorrect frame definition by frame editor, or
disagreement between communication command
and frame, or incorrectly connected cable. (Bad
connection with communication module)
CPU or communication module error
ERR-7
Monitor data is not correctly received
during TX monitor operation
•
Bad cable connection.
•
Disagreement of basic parameters between
PC and communication module.
[Table 11.5] NAK transmission during slave communication in dedicated mode
Error code
Error indication
Error contents
ERR-8
NAK frame is sent to as response to
request frame of other station. (NAK
LED(4,12) of Cnet I/F module flashes)
•
Protocol disagreement of dedicated communication
frame.
•
Bad cable connection.
•
Disagreement of communication basic parameters
[Table 11.6] No response during slave communication in dedicated mode
Error code
Error indication
Error contents
ERR-9
No response is sent to request frame of
other station.
•
Incorrectly specified station No. of frame editor.
•
Bad cable connection.
[Table 11.7] GMWIN connection error
Error code
Error indication
Error contents
ERR-10
Modem connection and initialization are
not performed.
•
Operation mode setting error in Cnet I/F module.
•
Disagreeable initialization command of modem.
•
Bad connection with cable and telephone line.