Chapter 7 Communication function
7-126
I) If connection is released , GMWIN hangs up the phone automatically to disconnect it.
J) If the phone is hung up normally, local and remote modem is restored to initial status to allow remote
connection again via telephoning.
2)
Dedicated modem connection
[Figure 7.24] shows dedicated modem connection between PC and Cnet I/F module via dedicated line, where Cnet
I/F module can be set to dedicated modem without telephoning stage differently from dial-up modem.
[Figure 7.24] Connection diagram via dedicated modem
[Figure 7.24] shows an example of dedicated modem connection via dedicated line or wireless modem / optical
modem available also. Modem without public line shall be set as in dedicated modem as follows. Refer to 4.4 How to
connect to modem in this manual for selection of dedicated modem connected with Cnet I/F module and
connection/setting of dedicated modem of Cnet I/F module.
Remote connection sequence via dedicated modem is as follows.
A) Connect dedicated modem between PC and Cnet I/F module.
B) Set RS-232C channel of Cnet I/F module to GMWIN mode.
C) Set RS-232C channel operation of Cnet I/F module to dedicated modem.
D) Run GMWIN program and select connection from project option to specify connection type. Set connection
type to modem and dedicated modem, and communication port and transmission speed which are set in
dedicated modem linked with PC. Communication speed shall be set same as in dedicated modem.
Dedicated line
Remote connection
Modem
Modem
rs-232c cable
RS-232C CABLE
Cnet