Chapter 8 Exercising program
8-22
2) Operation setting
Connect 9-pin to 25-pin cable with dial-up modem and Cnet I/F module via RS-232C channel in the following
type.
[Table 8.6] Modem connection with Cnet I/F module
Cnet (9-pin) male
Modem side(25-pin) male
Pin No.
Name
Connection No. and signal direction
Pin No.
Name
1 CD
CD 8
2 RXD
RXD 3
3 TXD
TXD 2
4 DTR
DTR 20
5 SG
SG 7
6 DSR
DSR 6
7 RTS
RTS 4
8 CTS
CTS 5
9 RI
RI
22
3) Modem initializing
If mode setting and connection between modem and Cnet I/F module via cable are completed, link phone line to
modem and let PLC powered on to initialize modem. Modem initializing is accomplished by modem initializing
command set previously in Cnet I/F module after powered on. If modem has been successfully initialized, Cnet
LED is displayed as below.
Cnet I/F module LED status in stand-by mode
G4L-CUEA
RS-232C
RS-422
RUN/BPS
TX/BPS
RX/BPS
ACK/DATA
NAK/PARITY
ERR/EVEN-ODD
MODEM/STOP
SYS-RUN
RUN/BPS
TX/BPS
RX/BPS
ACK/DATA
NAK/PARITY
ERR/EVEN-ODD
RS-485/STOP
SYS-ERR
The figure above shows the case that modem has been initialized normally. If not initialized, TX LED will flash in
a cycle of 1 sec. in the figure. If so, refer to Chapter 4 How to connect to dial-up modem in the manual to shoot
the trouble.
RUN/BPS : ALWAYS ‘ON’
MODEM/STOP : ALWAYS ‘ON’
SYS-RUN : DIMLY ‘ON’