Chapter 7 Communication function
7-67
1
Monitor registration(X##)
Monitor can be registered separately up to 32 combinations with reading command of actual variables and has a
function to monitor the applicable variable value through the number registered by monitor command after the
registration. The max. number available for monitor registration depends on the version of Cnet I/F module. The
max. number and registration variable number can be set via Frame Editor.
1)
Selection of the monitor registration number of Frame Editor
Setting screen of basic parameters in Frame Editor has a function to set the size of monitor registration to 4X32
or 16X20. 16X20 is only for Cnet I/F module Ver. 1.4 or later with the following differences.
9
4 X 32 : Registration number up to 32 is supported with max.4 variables available per monitor
registration and with max.‘4X32=128’ as the variable number available for the registration in all
Cnet versions not below than Ver.1.0.
9
16 X 20 : Registration number up to 20 is supported with max.16 variables available per monitor
registration and with max.‘16X20=320’ as the variable number available for the registration in
Cnet version 1.4 or later only.
9
G7L-CUEC : Registration number up to 10 is supported with max.16 variables available per
monitor registration and with max.‘16X10=160’ as the variable number available for the
registration, however NAMED variables are not supported..
2)
Request format(PC -> PLC)
Format
Name
Header
Station No.
Command
Registration
No.
Registration format
Tail
Frame check
Frame (Ex.)
ENQ
H10
X(x)
H1F
See registration format
EOT
BCC
ASCII value
H05
H3130
H58(78)
H3146
[
※
]
H04
9
BCC : When command is one of lower case(x), only one lower byte of the value resulted by adding 1 byte
each to ASCII values from ENQ to EOT is converted into ASCII and added to BCC.