Chapter 5 Frame Editor
5-41
4)
Set slot No.’0’ where Cnet I/F module is mounted and connection stage to remote in online mode change.
5)
Select desired type of channel operation from channels of interlocking and stand-alone.
[Note]
Remark
[Note1] Setting values are valid only in RS-232C channel for G6L-CUEB and only in RS-422 channel for
G6L-CUEC. In case of two types of modules, the operation isn’t available in interlocking mode.
Basic value if not set is user mode all for RS-232C/RS-422 in stand-alone channel.
6)
If mode is set as required, select Write button to change modes. If modes are changed, the following
message will be displayed to indicate operation mode completed.
[Note1]
Remark
[Note1] If mode change is written, communication of RS-232C/RS-422 channel is disconnected for approx.
1 second to convert operation into newly changed mode and then is automatically operated again
in changed mode after mode change is completed.