Chapter 7 Communication function
7-56
Data type
Flag name
Status data sequence(HEX data)
WORD
_SYS_STATE;
H06(L) ~ H07(H)
Byte _PADT_CNF;
H08
Byte _Domain_ST;
H09
WORD
_CNF_ER;
H0a(L) ~ H0b(H)
WORD
_CNF_WR;
H0c(L) ~ H0d(H)
WORD
Reserved
H0e(L) ~ H0f(H)
WORD
Reserved
H10(L) ~ H11(H)
Remark
[Note 1] For the details on each flag, see flag list in technical spec. of GLOFA PLC CPU. Do not process
PC_DEVICE_IDENTIFIER and Logical/Physical which are used as dedicated to system
3)
Response format(for PLC of NAK response)
Format
Name
Header
Station No.
Command
Command
type
Error code
(HEX 2 Byte)
Tail
Frame check
Frame(Ex.)
NAK H0A R(r) ST
H1132
ETX BCC
ASCII
value
15 3041 5272 5354
31313332
03
9
Station number, commands, and type of command are the same as in computer request format.
9
BCC : When command is one of lower case(r), only one lower byte of the value resulted by adding 1 byte
each to ASCII values from NAK to ETX is converted into ASCII, added to BCC, and sent.
9
Error code is HEX and 2 bytes(ASCII code, 4 bytes), which indicates type of error. For the details, see
Appendix ‘B. Error Code Table’.