Chapter 5 Frame Editor
5-42
7)
If the message below is shown, the mode switch of one Cnet I/F module is not No.9 online mode. Change
mode switch of Cnet I/F module to No.9 online mode, reset PLC and execute again from No. (1)
[Note]
Remark
[Note1] Both Cnet I/F modules of PLC-A/PLC-B shall be set to No.9 online mode.
8)
If the message below is shown, version of Cnet I/F module is below Ver.2.0. Online mode change is unavailable.
Remark
[Note1] Both Cnet modules of PLC-A/PLC-B shall be of Ver.2.0.
[Note2] Error above may occur where communication error is expected in status of modem communi-
cation.
[Note3] If communication in a cycle of within 20msec is overloaded, set CPU mode of PLC to Stop and
then change the operation mode. Where communication is overloaded, error in mode change may
occur.
9)
The changed mode is saved in flash memory of module as kept even if powered off.