Chapter 3 Product specification
3-3
Item
Specification
Remark
Transmission
distance
RS-232C : Max. 15m(extendible by using modem)
RS-422 : Max. 500m
GM3/4/6/7
Diagnosis function
Loop-Back diagnosis / Indication of operation status with 16 LEDs during
operation (with 8 LEDs for GM6)
GM3/4/6
G3L-CUEA
160mA or less
G4L-CUEA
160mA or less
Current
G6L-CUEB
160mA or less
Consumption
G6L-CUEC
160mA or less
G7L-CUEB
100mA or less
G7L-CUEC
100mA or less
G3L-CUEA
375g
G4L-CUEA 211g
Weight
G6L-CUEB
94g
G6L-CUEC 102g
G7L-CUEB 195g
G7L-CUEC 193g
Remark
[Note1] With Frame Editor, RS-422 channel of GM3/4/6 can be selected from RS-422 or RS-485. In case of GM7,
auto-setting is performed by the wiring of communication module on basic unit.
[Note2] In case of connecting channel RS-232C to modem, the modem connection is selected in setting menu of
RS-232C communication type of Frame Editor. (G6L-CUEC is unavailable)
[Note3] Regardless of Version, only Modbus interface function is supported for GM7.
[Note4] Transmission spec. can be set according to each of RS-232C and RS-422 in case of the operating mode of
the stand-alone channel.
[Note5] Channel selection is set between operating mode by channel and stand-alone/interlocking channel by the
operating mode switch. Change of channel mode is impossible during operation.
[Note6] 76,800bps is provided in RS-422 or RS-485, and can be used in Cnet I/F module Ver. 1.3 or later.