Troubleshooting Guide
- 78 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Defective temperature sensor con-
nection
2. Defective temperature sensor
(Open / Short)
3. Defective outside unit PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal sensor resistance value
(Open/Short)
Outside unit liquid pipe
(condenser) temperature
sensor error
113*
■
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Is the value of temperature
sensor resistance normal?*
Check and correct connection
Replace sensor
Replace outside unit PCB
Yes
Yes
No
No
* Sensor resistance 100kΩ over (open) or 100Ω below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outside unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ
Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ