- 18 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
2.1 Oil return control
2.1.1 Oil return control on cooling mode
Oil return operation recovers oil amount in compressor by collecting oil accumulated in pipe.
Each cycle component operates as following table during oil return operation.
■
Oil return operation time : 3min for running step
■
Starting condition:every 3hours operate
■
Oil return process ends if compressor protection control starts
Normal control
OFF
Max. pulse
40Hz
Ending
Normal control
OFF
Max. pulse
Setting Value
Running
Normal control
OFF
Max. pulse
25Hz
Starting
Hot gas bypass valve
4way valve
Main EEV
Inv Compressor
Component
OFF
Min. pulse
Normal control
Ending
ON
1200 pulse
1200 pulse
Running
OFF
Min. pulse
Normal control
Starting
Oil return signal
Thermo off unit EEV
Thermo on unit EEV
Component
Outside Unit
Indoor Unit
2. Special control
Function