Checking Method for Key Components
EEV
M
1
3
5
2
6
4
ø5
Red
White
Yellow
Orange
Blue
5
4
3
2
ø4
DC 12V
Driving%
circuit
ø3
ø2
ø1
1
ø4
ø3
ø2
ø1
• Pulse signal output value and valve operation
• Output pulse sequence
- In valve close state: 1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
→
9
→
10
→
11
→
1
- In valve open state: 11
→
10
→
9
→
8
→
7
→
6
→
5
→
4
→
3
→
2
→
1
→
11
* 1. If EEV open angle does not change, all of output phase will be OFF
2. If output phase is different or continuously in the ON state, motor will not operate smoothly and start
vibrating.
• EEV valve operation
ø1
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ø2
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
ø3
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ø4
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
Output (ø) No.
Output state
1
2
3
4
5
6
7
8
9
10
11
Valve%
open%
Angle
close
pulse
open
Full open%
1350 pulses
- At power ON, open angle signal of 1400 pulses out-
put and valve position is set to
ⓐ
If valve operates smoothly, no noise and vibration
occurs and if valve is closed. noise occurs.
- Noise from EEV can be confirmed by touching the
EEV surface with a screw driver and listening the
EEV noise.
- If liquid refrigerant is in EEV, the noise is lower.
2.2 Electronic Expansion Valve