3.2 Discharge temperature control
■
Outside unit control
■
Indoor unit control
3.3 Inverter protection control
- 22 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Function
Temperature Range
Compressor
Td ≥ 115℃
System stop
105℃ < Td < 115℃
Frequency down
Td ≥ 105℃
Pressure control
Temperature Range
EEV
Td ≥ 115℃
System stop
95℃ < Td < 115℃
Emergency SH control
90℃ < Td ≤ 95℃
Keep current control
Td ≤ 90℃
SH control
Normal Operation
Frequency Down
System Stop
AC Input Current
15.5A or less
16A or more
25A or more
Compressor Current
(Cooling/Heating)
23/26A or less
23/26A or more
29A or more