Test Run
Test Run
1
2
3
4
Check to see whether there is any refrigerant leakage, and slack of power or transmission cable.
Confirm that 500 V megger shows 2.0MΩ or more between power supply terminal block and ground.
Do not operate in the case of 2.0MΩ or less.
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board
would be broken.
Immediately after mounting the unit or after leaving it turned off for an extended length of time,
the resistance of the insulation between the power supply terminal board and the ground may
decrease to approx. 2MΩ as a result of refrigerant accumulating in the internal compressor.
If the insulation resistance is less than 2MΩ, turning on the main power supply and energizing
the crankcase heater for more than 6hours will cause the refrigerant to evaporate, increasing
the insulation resistance.
Check if high/low pressure common pipe, liquid pipe and gas pipe valves are fully opened.
NOTE: Be sure to tighten caps.
Check if there are any problems in automatic addressing or not:
Check and confirm that there are no error messages in the display of indoor units or remote controls
and LED in outside units.
1. Checks Before Test Run
CAUTION
when cutting main power of the Multi V
• Always apply main power of the outside unit during use of product
(cooling season/heating season).
• Always apply power before 6hours to heat the crank case heater where performing test run after
installation of product. It may result in burning out of the compressor if not preheating the crank
case with the electrical heater for more than 6hours.(In case of the outside temperature below 10°C)
• When operating the unit after powering off, automatically run into in the preheat mode for 3hours
and "PH" is indicated on the outside unit 7-Segment.
CAUTION
Preheat of compressor
• Start preheat operation for 3hours after supplying main power.
• In case that the outside temperature is low, be sure to supply power 6hours before operation so
that the heater is heated(insufficient heating may cause damage of the compressor.)