Troubleshooting Guide
- 64 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
■
Error diagnosis and countermeasure flow chart
1. Defect of high pressure sensor
2. Defect of indoor or outside unit fan
3. Deformation because of damage of refrigerant pipe
4. Over-charged refrigerant
5. Defective indoor / outside unit EEV
6. When blocked
- Outside unit is blocked during cooling
- Indoor unit filter is blocked during heating
7. SVC valve is clogged
8. PCB defect of outside unit
10. Indoor unit pipe temperature sensor defect
Error
No.
Error Type
Error Point
Main Reasons
Error happens
because of 3 times
successive compres-
sor off due to over-
increase of high pres-
sure by high pressure
sensor
Over-increase of dis-
charge pressure of
compressor
34*
Is service valve opened ?
No
Open service valve
Are transmission
cable / pipe connection
normal?
Yes
No
Is refrigerant
amount normal?
[refer refrigerant part]
Yes
No
Is fan normal?
(Indoor fan during heating
Outside fan during cooling)
Yes
No
Yes
Adjust refrigerant amount
Check and repair transmission
cable / pipe connection
Replace related parts
(Refer to Error 105~107)
Is filter blocked
(Heating:indoor,
Cooling:outside
heat exchanger)?
No
Clean indoor filter (heating)
/outside heat exchanger (cooling)?
Is value of high pressure
sensor same as Manifold
value(Is it high actually)?
No
Replace sensor of high pressure
Yes
Yes
Check indoor unit LEV
Check indoor unit PCB
Check in/outside installation
condition
Summary of Contents for ARWN038GA2
Page 81: ...P NO MFL67101202 APRIL 2013 ...