Troubleshooting Guide
- 66 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
40*
Inverter compressor CT
sensor error
Error
No.
Error Type
Error Point
Main Reasons
Micom input voltage isn't
within 2.5V ±0.3V at initial
state of power supply
1. Input voltage abnormal (T-N)
2. ODU inverter PCB damage
(CT sensing part)
■
Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
No
Yes
Recheck power and installation condition
Check
R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
’
Check connection condition and wiring if power is
abnormal
Is inverter PCB assembly normal?
No
Yes
Replace inverter PCB assembly
* Measuring input voltage
* Inverter PCB assembly
* LGMV Part
Summary of Contents for ARWN038GA2