4.2 Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, Outside unit parts
replacement or IDU addition/replacement.
Master Main PCB D/W ON (No.11,14)
Vacuum mode setting
Outside unit V/V OPEN
Main Lev, SC Lev OPEN
IDU Lev OPEN
Outside unit power reset
Press the black button Main PCB (5sec.)
Main PCB
SW01S
Main PCB
SW02B
Main PCB
SW01V
Outside unit operation stops during vacuum mode. Compressor can't operate.
Vacuum mode setting method
Vacuum mode cancellation method
Master Main PCB D/W OFF (No.11,14)
Power Reset
Vacuum Mode cancellation
Caution
Function