Checking Method for Key Components
2.3 Inverter IPM Checking Method
1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN-P1, CN-N1 connectors and U,V,W COMP connector connected with the inverter PCB.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short (0Ω) or open (hundreds MΩ), PCB needs to be
replaced. (IPM damaged)
5. In the measured value with resistance mode should be within 28kΩ ±10%.
6. In case measured value is different from the table, PCB needs to be replaced. (PCB damaged)
✽
Red (+) and black (-) are the measuring terminals of multi tester.
P terminal : black (-)
N terminal : red (-)
U terminal : red (+)
28kΩ ± 10%
Open
V terminal : red (+)
28kΩ ± 10%
Open
W terminal : red (+)
28kΩ ± 10%
Open
P terminal : red (+)
N terminal : red (+)
U terminal : black (-)
Open
28kΩ ± 10%
V terminal : black (-)
Open
28kΩ ± 10%
W terminal : black (-)
Open
28kΩ ± 10%