Troubleshooting Guide
- 73 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
60*
Inverter PCB EEPROM
error
Error
No.
Error Type
Error Point
Main Reasons
EEPROM Access error and
Check SUM error
1. EEPROM contact defect/wrong insertion
2. Different EEPROM Version
3. ODU inverter PCB assembly damage
■
Error Diagnosis and Countermeasure Flow Chart
Is EEPROM insertion normal?
No
Yes
Recheck power and installation condition
1.Check EEPROM insert direction/connection condition
2.Check EEPROM Check SUM
→
Replace if abnormality found
Is inverter PCB assembly normal?
No
Yes
Replace inverter PCB assembly
* Inverter EEPROM inserting point
* Right inserting direction of inverter EEPROM
❊
Note : Replace after power off
EEPROM enlarged picture