Troubleshooting Guide
- 67 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Defective connection of the
compressor discharge pipe tem-
perature sensor
2. Defective discharge pipe com-
pressor sensor of the compres-
sor (open/short)
3. Defective outside PCB
Error No.
Error Type
Error Point
Main Reasons
Sensor measurement
valve is abnormal
(Open/Short)
Compressor dis-
charge pipe tem-
perature sensor
error
41*
(Inverter)
■
Error diagnosis and countermeasure flow chart
Check the resistance
inverter compressor
discharge temperature
sensor
Sensor connection to PCB
is normal?
Is the resistance of
sensor normal?*
Insert sensor connector to PCB properly
Replace sensor
Replace corresponding outside PCB
Yes
No
No
Is sensor resistance
value same as temperature
value of LGMV?
Yes
Yes
No
Replace corresponding sensor
Check the resistance
of constant compressor
discharge temperature
sensor
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
Note: Standard values of resistance of sensors at different temperatures (5% variation)
10C = 362k : 25C= 200k : 50C= 82k : 100C= 18.5k