Function
2) Step 2 : Communication check
- If all model code is displayed in 7-segment communication between outdoor units is normal.
- If 104* is displayed in 7-segment, check communication wires between outside units and Dip switch setting.
3) Step 3 : PCB error check
- After 40sec, error check begins.
4) Step 4 : Auto addressing of indoor units
- Auto addressing begins when address(red) button in Main PCB is pressed for 6sec.
- During auto addressing, 7-segment on main PCB displays "88"
- After auto addressing, the number of indoor units is displayed in 7-segment for 30sec. The address of each
indoor unit is displayed on each wired remote controller.
Push address(red) button for 6sec.
Auto address starts
Auto address is in progress (max. 15min.)
The number of indoor units is displayed for 30sec.
(9 indoor units found)
Auto address process is finished.
Every indoor unit displays its address on
wired remote controller and the 7segment of
main PCB is off.
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
7
8
9 10 11 12 13 14
6sec.