2.1.2 Oil return control on heating mode
■
Oil return operation time : 3min for running step
■
Starting condition:same as cooling mode
■
Oil return process ends if compressor protection control starts
Outside Unit
Indoor Unit
OFF
Min. pulse
Normal control
Ending
ON
1200 pulse
1200 pulse
Running
OFF
Min. pulse
Normal control
Starting
Hot gas bypass valve
4way valve
Main EEV
Inv Compressor
Component
Normal control
OFF
Max. pulse
25Hz
Starting
Normal control
OFF
Max. pulse
Setting Value
Running
Normal control
ON
Max. pulse
25Hz
Ending
Oil return signal
Thermo off unit EEV
Thermo on unit EEV
Component
Function