Load Wiring
To ensure that the functions of the PLZ-U work accurately and reliably, all wires
must be connected correctly to their loads.
2.7.1
Precautions Concerning Wiring
■
Electric wire used
• Use a load wire with suf
fi
cient diameter for the current as well as non-
fl
am-
mable or
fl
ame-resistant cover.
If the resistance of the load wire is large, a large voltage drop may occur when a cur-
rent is supplied and the voltage at the load input terminal may fall below the mini-
mum operating voltage. Refer to Table 2-1 and select as thick wires as possible.
Table2-1
Nominal cross-sectional area of wires and allowable
currents
Nominal
Cross-Sectional Area
[mm
2
]
AWG
(Reference
Cross-Sectional Area)
[mm
2
]
Allowable Current(*)
[A]
(Ta = 30
°
C)
Kikusui-
Recommended Current
[A]
2
14
(2.08)
27
10
3.5
12
(3.31)
37
-
5.5
10
(5.26)
49
20
8
8
(8.37)
61
30
14
6
(13.3)
88
50
22
4
(21.15)
115
80
30
2
(33.62)
139
-
38
1
(42.41)
162
100
50
1/0
(53.49)
190
-
60
2/0
(67.43)
217
-
80
3/0
(85.01)
257
200
100
4/0
(107.2)
298
-
125
-
-
344
-
150
-
-
395
300
200
-
-
469
-
250
-
-
556
-
325
-
-
650
-
* Excerpts from Japanese laws related to electrical equipment.
CAUTION
Summary of Contents for PLZ-30F
Page 32: ...2 18 Installation and Preparation PLZ U ...
Page 58: ...4 14 Basic Operation PLZ U ...
Page 144: ...6 52 Remote Control PLZ U ...
Page 145: ...PLZ U Maintenance 7 1 Chapter 7 Maintenance This chapter explains the PLZ U maintenance 7 7 ...
Page 186: ...A 26 Appendix PLZ U ...
Page 190: ...I 4 Index PLZ U ...
Page 191: ......