Operation Manual ServoOne Supply Unit
83
ID no.: 1101.21B.6-00 Date: 04/2020
A.8 Technical data, input choke
For size
BG5
BG6a
For device
SO84.040
SO84.076
SO84.115
SO84.170
Rated AC current
3 x 40 A
3 x 76 A
3 x 115 A
3 x 170 A
Supply voltage
3 x 400 VAC ... 3 x 480 VAC
Power dissipation
at 100 % duty factor
120 W
144 W
180 W
174 W
Frequency
50/60 Hz
Protection
IP00, installation in a switch cabinet necessary
Installation position
Capacitors with liquid or viscous filling must be installed upright with terminals
pointing upward.
Power connections
Cable cross-section
(flexible without / with
ferrule)
1.5...16 mm
2
1.5...16 mm
2
(AWG 18...
AWG 6)
2.5...35 mm
2
2.5...35 mm
2
(AWG 12...
AWG 0)
2.5...35 mm
2
2.5...35 mm
2
(AWG 12...
AWG 0)
16...120 mm
2
16...95 mm
2
(AWG 4... 250
kcmil)
Tightening torque
1.5...2.4 Nm
(13.2...21.2 lb-in)
4...5 Nm
(35.4...44.2 lb-in)
4...5 Nm
(35.4...44.2 lb-in)
12...20 Nm
(106.2...177 lb-
in)
Table A.20 Technical data, input choke
For size
BG7
For device
SO84.375.S
SO84.540.S
Rated AC current
3 x 375 A
3 x 540 A
Supply voltage
3 x 400 VAC ... 3 x 480 VAC
3 x 400 VAC ... 3 x 480 VAC
Designed for active power (step-up
operation 650 VDC/770 VDC)
250 kW
360 kW
Power dissipation at 100 % duty factor
714 W
1050 W
Frequency
50/60 Hz
50/60 Hz
Connection to copper straps
Cable lug
Cable lug
Protection
IP00, installation in a switch cabinet necessary
Temperature sensor
KTY84-130
KTY84-130
Power connections
Connection lug for ring cable lug
Ø 13 mm
2
Screws for ring cable lug
The screw size and tightening torque depend on the ring cable lug
used.
Tightening torque
KTY sensor
Cable cross-section (flexible with ferrule)
0.5...2.5
mm
2
(AWG 20...AWG 13)
Tightening torque
0.4...0.8 Nm (3.5...7.0 lb-in)
Table A.19 Technical data, step-up choke
Appendix
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...