Operation Manual ServoOne Supply Unit
16
ID no.: 1101.21B.6-00 Date: 04/2020
1
ON
0
OFF
0
PW
R
LOC
K
CF
Pow
er
Rese
t
RJ-45/Lin
e
RS 23
2
COM
Data
Statu
s
< 200 mm
< 20
1
7
8
6
5
4
3
2
12
9
10
10
10
10
11
14
13
Key
1) Mains cable
2) Main switch
3) Fuses
4)
Mains filter
Cables without interference suppression must be laid at
a distance of at least 200 mm from the mains input side
of the filter so that no interference can be coupled into
the cables.
5) Circuit breaker
6) Mains contactor
7) Input choke with capacitor connected
8) Step-up choke
9) ServoOne supply unit
10) ServoOne DC axis controller
11) DC power supply via DC link cable
12) Braking resistor
13) Motor cables
14) Controller
Figure 3.1 Example: arrangement in the switch cabinet
3.2
Switch cabinet layout
The positioning of the components in the switch cabinet has a significant effect on the
trouble-free system and machine function. You should take into account the following
points in your planning:
y
Evaluate the assemblies used in relation to EMC.
y
Divide the switch cabinet into zones with different power and interference levels.
y
For devices susceptible to interference, maintain a distance of at least 200 mm
from the following components:
− Drive controller
− Input and output chokes, transformers
− Mains, motor, DC power supply and braking resistor cables (even if shielded)
− Relay and contactors (even if interference-suppressed)
y
For small distances use separators for shielding; fasten the separators directly
and conductively to the backing plate.
y
If a motor contactor or motor choke is used, the component should be
positioned directly at the drive controller.
y
Do not use fluorescent lamps in switch cabinets, as they emit high-frequency
interference.
y
Fit contactors, relays, solenoid valves, switched inductors and capacitors with
suppressors.
y
The mains filter must be mounted on the backing plate as close as possible to
the feed point and with large surface area contact. The backing plate must be
connected to the central earthing point with a low-impedance connection.
No unfiltered cables are allowed to be laid on the mains input side of the filter so
that no interference can be coupled into the cables.
Mechanical installation
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...