Operation Manual ServoOne Supply Unit
43
ID no.: 1101.21B.6-00 Date: 04/2020
PE
GNDµP
DGND complex,
non-lineare
impedance
RC ethernet Polyswitch
GNDµP
GNDµP
GNDµP
X4/15
ISD00
ISD01
I
LIM
X4/21
ISD06
I
LIM
X4/10
ENPO
I
LIM
X4/22
ISDSH
I
LIM
X4/7
OSD00
X4/3
ISA00+
X4/4
ISA00-
ISD02
ISD03
ISD04
ISD05
A/D
A/D
ISA01+
X4/5
X4/6
ISA01-
X4/14
GNDµP
GNDµP
DGND
DGND
DGND
DGND
DGND
DGND
DGND
DGND
X4/2
ϑ
F1
ϑ
F2
X4/13
DGND X4/1
ϑ
F3
ϑ
F3
ϑ
F4
V
µP
µP
X4/8
OSD01
X4/9
OSD02
RSH
X4/12
X4/11
OSD04
X4/23
X4/24
USB1.1
X2
Ethernet
X3
Mains synchronization
X21
GNDµP
V
µP
PE
U
V
U
V
X9/+
X9/-
X10/+
X10/-
U
H
Control
supply
24 V DC
Control
supply
24 V DC
KTY temperature sensor
for set-up reactor
GNDµP
V
µP
X5/
ϑ +
X5/
ϑ −
*)
*)
*)
*) For BG5, also connect the 24 V DC control supply to control terminals. Internal connection is not available.
Figure 4.17 Electrical isolation concept, BG5 and BG6a
4.6 Electrical isolation concept
The control electronics with their logic (µP), the inputs and outputs, are electrically
isolated from the power section (power supply/DC link). All control connections are
designed as safety extra low voltage/protective extra low voltage (SELV/PELV) circuits
and are only allowed to be operated with 5 V to 50 V as per the relevant specification.
This provides reliable protection against electric shock on the control side. The
control electronics therefore require a separate control supply that corresponds to the
requirements of a SELV/PELV.
The overview opposite shows the potential references for the individual connections in
detail. This concept also delivers higher operational safety and reliability of the supply
unit.
SELV = Safety Extra Low Voltage
PELV = Protective Extra Low Voltage
NOTe:
The terminal X5 (for KTY on the step-up choke) represents a special case in
relation to insulation and isolation.
The temperature sensor for the step-up choke must be designed as a minimum
with a basic insulation in relation to the choke winding as per EN61800-5-1.
Electrical installation
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...