Operation Manual ServoOne Supply Unit
53
ID no.: 1101.21B.6-00 Date: 04/2020
Value
Value name
Description
11
OUTPUT_FS_UDC_LIM_AC-
TIV
Setpoint limiting for the DC link voltage active (the
voltage is outside the defined range.)
12
OUTPUT_FS_I_LIM_ACTIV
No function
13
OUTPUT_FS_ENMO
No function
14
OUTPUT_FS_PLC
No function
15
OUTPUT_FS_WARN
General warning
16
OUTPUT_FS_WUV
Warning, undervoltage in the DC link
(defined in P-0730[0,1])
17
OUTPUT_FS_WOV
Warning, overvoltage in the DC link
(defined in P-0730[2,3])
18
OUTPUT_FS_WIIT
Warning, I2t power stage protection threshold reached
(defined in P-0730[6,7])
19
OUTPUT_FS_WOT_PTC
Warning KTY sensor for step-up choke
(defined in P-0730[12,13])
20
OUTPUT_FS_WOTI
Warning, supply unit heat sink temperature (defined in
P-0730[08,9])
21
OUTPUT_FS_WOTD
Warning, supply unit internal temperature (defined in
P-0730[10,11])
22
OUTPUT_FS_WLIS
Warning, apparent current limit exceeded (defined in
P-0730[4,5])
23
OUTPUT_FS_WLVOLT
Warning, DC link voltage limit exceeded (defined in
P-0730[14,15])
24
OUTPUT_FS_COM_1MS
Set the outputs via COM option in 1 ms cycle
25
OUTPUT_FS_COM_NC
Set the outputs via COM option in NC cycle
26
OUTPUT_FS_SH_S
No function
27
OUTPUT_FS_BC_FAIL
Brake chopper fail error (error = LOW)
28
OUTPUT_FS_WLPOW
Active power limit exceeded
(defined in P-0730[16,17])
29
OUTPUT_FS_GRID_OK
Mains OK (frequency AND voltage within the tolerance
window = HIGH)
Table 4.12 Functions that can be selected for the digital outputs OSD00 to OSD02
4.10 Functions of the digital inputs
The following functions can be selected for the digital inputs ISD00 to ISD06:
Value
Value name
Description
0
MPRO_INPUT_FS_OFF
No function
1
MPRO_INPUT_FS_START
Start regulation
2
MPRO_INPUT_FS_E_EXT
External error on another device
3
MPRO_INPUT_FS_WARN
External warning on another device
4
MPRO_INPUT_FS_RSERR
Reset error message
Table 4.11 Functions that can be selected for the digital inputs ISD00 to OSD06
4.11 Functions of the digital outputs
The following functions can be selected for the digital outputs OSD00 to OSD02:
Value
Value name
Description
0
OUTPUT_FS_OFF
No function
1
OUTPUT_FS_ERR
General error
2
OUTPUT_FS_ACTIV
Regulation in operation
3
OUTPUT_FS_S_RDY
Device initialised
4
OUTPUT_FS_PRE-
CHARGE_RDY
Device precharged
5
OUTPUT_FS_C_RDY
Device ready
(DC link voltage present)
6
OUTPUT_FS_REF
Setpoint for the DC link voltage reached
7
OUTPUT_FS_E_FLW
No function
8
OUTPUT_FS_LIMIT
Setpoint limiting for the DC link voltage active (the
voltage is outside the defined range.)
9
OUTPUT_FS_UDC_GT_
UDCX
Actual value of the DC link voltage is higher than de-
fined in parameter P-0740 voltage threshold
10
OUTPUT_FS_P_LIM_ACTIV
No function
Electrical installation
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...