Operation Manual ServoOne Supply Unit
77
ID no.: 1101.21B.6-00 Date: 04/2020
Size
BG7
Device
SO84.375.S
SO84.540.S
Mains input voltage (±10%)
[VAC]
400
460 /
480
400
460 /
480
Regulated DC link voltage [VDC]
650
770
770
650
770
770
Input, mains side
Continuous current [AAC
eff
]
375
375
313
540
540
450
Peak current
1)
[AAC]
565
565
470
565
565
565
Switching frequency [kHz]
4
4
Continuous power [kW]
260
374
Power dissipation
2)
[W]
3300
4100
Asymmetry of the mains voltage
± 3 % max.
Frequency [Hz]
50/60
DC link output
Continuous current [ADC]
385
325
325
553
468
468
Peak current
1)
[ADC]
577
487
487
577
487
487
Continuous power [kW]
250
360
Peak power
1)
[kW]
375
375
DC link capacitance [µF]
7200
Note: Technical data apply for power stage switching frequency 4 kHz and as a function of the mains input voltage and the
regulated DC link voltage
1) For 10 s
2) Approximate values
Table A.7 Technical data, BG7
Connection
Size
BG6a
Device
SO84.115
SO84.170
X11/L+, L-
Cable cross-section
Use the pre-assembled connection cables supplied or
35...95 mm
2
(AWG 2...AWG 3/0)
1)
Tightening torque
25...30 Nm (221...265 lb-in)
X11/PE
Screw size for ring
cable lug
M8
Tightening torque
10...12 Nm (88...106 lb-in)
X12/L1, L2, L3
Cable cross-section
50...150 mm
2
(10...95 mm
2) 2)
(AWG 0...AWG 5/0)
1)
50...150 mm
2
(AWG 0...AWG 5/0)
1)
Tightening torque
25...30 Nm (221...265 lb-in)
X12/PE
Cable cross-section
35...95 mm
2
(AWG 2...AWG 3/0)
1) 3)
Tightening torque
25...30 Nm (221...265 lb-in)
X12/RB+, RB-
Cable cross-section
25...50 mm2
(AWG 4...AWG 0)
1)
Tightening torque
6...8 Nm (53...70 lb-in)
X12/ZK+, ZK-
Cable cross-section
50...150 mm
2
(AWG 0...AWG 5/0)
1)
Tightening torque
25...30 Nm (221...265 lb-in)
1) Flexible cable with/without ferrule
2) With optional profile inserts on SO84.115.Sxxx.x to reduce the diameter
3) The protective earth conductor cross-section depends on the cross-section of the phase conductor (see chap. 4.5, p. 40)
The minimum cross-section of the connection cables depends on the local regulations, conditions as well as on the rated
current of the supply unit.
Table A.6 Terminals, BG6a
Appendix
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...