Operation Manual ServoOne Supply Unit
52
ID no.: 1101.21B.6-00 Date: 04/2020
4.9.2
Standard terminal assignment
Terminal assignment with the factory setting
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
REL
REL
ISDSH
ISD06
ISD05
ISD04
ISD03
ISD02
ISD01
ISD00
+24 V
DGND
RSH
RSH
ENPO
OSD02
OSD01
OSD00
ISA1-
ISA1+
ISA0-
ISA0+
+24 V
DGND
Des.
Des.
X4
X4
ENPO
Figure 4.25 Control terminals, standard assignment (initial commissioning)
NOTe:
The safety function STO (Safe Torque OFF) is not required for the ServoOne
supply unit, as no motors are connected. To be able to start the supply unit, a
jumper must be placed between X4/14 and X4/22.
The safety function STO is used for ServoOne DC axis controllers.
Des.
Term.
Specification
Electrical isolation
Relay outputs
REL
REL
ISDSH
ISD06
ISD05
ISD04
ISD03
ISD02
ISD01
ISD00
+24V
DGND
RSH
RSH
ENPO
OSD02
OSD01
OSD00
ISA1-
ISA1+
ISA0-
ISA0+
+24V
DGND
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
X4
REL
X4/23
X4/24
•
Relay, 1 NO contact
•
Functions can be selected as for
digital outputs
•
25 V / 1.0 A AC, cos
ϕ
= 1
•
30 V / 1.0 A DC, cos
ϕ
= 1
•
Switching delay approx. 10 ms
•
Cycle time 1 ms
X4:23
X4:24
Yes
RSH
RSH
X4/11
X4/12
No function
Yes
Auxiliary voltage
+ 24 V
X4/2
X4/14
•
Auxiliary voltage for supplying the digital
control inputs
•
U
H
= U
V
-∆U (∆U typically approx. 1.2 V),
no irreparable damage in event of short
circuit
•
(+24 V -> GND), however device may
shut down briefly.
•
I
max
= 80 mA (per pin) with self-resetting
circuit breaker (polyswitch)
Yes
Digital ground
DGND
X4/1
X4/13
• Reference ground for 24 V, with self-resetting
circuit breaker (polyswitch)
Yes
Table 4.10 Specification of the control connections
NOTe:
If high currents flow via the ground terminals, high-impedance isolation from
the device ground due to the self-resetting fuse is possible. This can result in
the malfunction of the system (avoid currents circulating in the wiring).
Electrical installation
Summary of Contents for ServoOne Series
Page 6: ...Operation Manual ServoOne Supply Unit 6 ID no 1101 21B 6 00 Date 04 2020 Table of contents ...
Page 10: ...Operation Manual ServoOne Supply Unit 10 ID no 1101 21B 6 00 Date 04 2020 ...
Page 90: ...Operation Manual ServoOne Supply Unit 90 ID no 1101 21B 6 00 Date Date 04 2020 Glossary ...
Page 91: ...Operation Manual ServoOne Supply Unit 91 ID no 1101 21B 6 00 Date 04 2020 ...