Appendix A _________________________________ Probe Installation Kits and Installation Examples
JUMO _________________________________________________________________________ 169
Example of Installation Through
Roof
1
2
3
4
5
6
7
8
9
10
11
12
Outdoor
environment
Process:
For example
+85 ºC, 85 %RH
0507-015
Figure 91
Example of Installation through Roof
The following numbers refer to Figure 91:
1
=
Insulated probe cables
2
=
Sealings
3
=
Roof
4
=
Cable gland for temperature probe (for example: AGRO 1100.12.91.065)
5
=
Temperature probe
6
=
Relative humidity probe
7
=
Cable gland for relative humidity probe (for example: AGRO 1160.20.145)
8
=
Plastic adapter to protect probes from condensation water coming from the
pipe. Diameter slightly smaller than tube diameter.
9
=
Plastic tube for probe (2 pcs)
10 =
Stainless steel tube coming through the roof.
11 =
Two thread bars holding the plastic adapter.
12 =
Insulated pipe ending.