User's Guide _______________________________________________________________________
128 ______________________________________________________________________________
PUR
Type
PUR
and press ENTER to proceed. The maximum interval is
14400 minutes (=10 days).
Example:
>pur
Interval Purge : OFF ?
Interval : 720 min ?
Power-up Purge : OFF ?
Duration : 120 s ?
Settling : 240 s ?
Temperature : 160 'C ?
Temp. diff. : 0.5 'C ?
>
NOTE
To activate the new interval settings immediately, reset the
transmitter.
NOTE
When chemical purge in power-up is enabled, wait about 6 min after
power-up before taking measurements. The output channels are
locked for the first operation minutes to the initial measured values