Chapter 4 _________________________________________________________________ Operation
JUMO _________________________________________________________________________ 121
where
b
=
bit rate (300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 115200)
p
=
parity (n = none, e = even, o = odd)
d
=
data bits (7 or 8)
s
=
stop bits (1 or 2)
ECHO
Use the
ECHO
command to enable/disable echo of characters
received over the serial line.
ECHO
[
x
]
where
x
=
ON/OFF (default = OFF)
When using 2-wire connection, echo must be always disabled.
SMODE
Use the
SMODE
command to set the default serial interface mode.
SMODE
[
xxxx
]
where
xxxx
= STOP, RUN or POLL
In STOP mode:
measurements output only by command SEND, all
commands can be used
In RUN mode:
outputting automatically, only command S can be
used to stop.
In POLL mode:
measurements output only with command SEND
[
addr
].
When several transmitters are connected to the same line, each
transmitter must be entered an own address in the initial configuration,
and POLL mode must be used.