User's Guide _______________________________________________________________________
112 ______________________________________________________________________________
Analog Output Fault Indication
Setting
Factory default state for analog outputs during error condition is 0 V/
0 mA. Please be careful when selecting the new error value. The error
state of the transmitter should not cause unexpected problems in
process monitoring.
Use the display/keypad to set the analog output fault indication.
1.
Press any of the arrow buttons to open the
MAIN MENU.
2.
Select
Interfaces
by pressing the ► arrow button.
3.
Select
Analog Outputs
by pressing the ► arrow button.
4.
Select
Output 1/2/3
by pressing the ► arrow button.
5.
Select Fault indication. Press
SET
to confirm your selection.
Enter the fault indication value by using the arrow buttons. Press
OK
to confirm your setting. This value is outputted if a
transmitter error occurs.
6.
Press
EXIT
to return to the basic display.
AERR
Use the serial line
AERR
command to change the error output.
AERR
Example:
>aerr
Ch1 error out : 0.000V ? 5.0
Ch2 error out : 0.000V ? 5.0
>
NOTE
The error output value must be within a valid range of the output
mode.
NOTE
The error output value is displayed only when there are minor
electrical faults such as humidity sensor damage. When there is a
severe device malfunction, the error output value is not necessarily
shown.