Appendix A _________________________________ Probe Installation Kits and Installation Examples
JUMO _________________________________________________________________________ 163
APPENDIX A
PROBE INSTALLATION KITS AND
INSTALLATION EXAMPLES
Duct Installation Kits (for 907023/333/337/335)
Duct installation kit includes a flange, a sealing ring, a supporting bar,
a probe attaching part, and screws for attaching the flange to the duct
wall.
0508-021
Figure 82
Duct Mounting Installation Kit
The following numbers refer to Figure 82:
1
=
Duct wall
2
=
Flange
3
=
Sealing ring
4
=
Supporting bar (not included in the kit for 907023/335)
5
=
Probe attaching part (to be fixed with the supporting bar)
6
=
Relative humidity probe
NOTE
When the temperature difference between the duct and the air outside the
duct is remarkable, the supporting bar must be installed as deep in the duct
as possible. This prevents errors caused by the heat conduction in the bar