7.2. Use of external sensors with the JA-60N
The JA-60N detector can be used to wire external sensors which have contacts on
their outputs. For example, it can be used to protect multiple doors or windows (see
fig. 16). The built in magnetic sensor of the JA-60N can also be disabled (DIP switch
number 2 to position ON) and then the JA-60N works only as an interface for exter-
nal sensors. Two input loops (TAMP & INP terminals) are activated when discon-
nected from the GND terminal.
INP
– when this input is triggered (disconnected from GND), the JA-60N will send the
same information as if the built in magnetic sensor was triggered. Reaction of the sys-
tem can be selected with DIP switch number 1 (ON= instant or 1= delayed).
TAMP
– when this input is triggered (disconnected from GND), the unit will send the
same information as if the built in tamper sensor was triggered.
Balanced loops
– the inputs INP & TAMP can also work as balanced loop inputs for
higher security of connected cables. If you install an End Of Line resistor 10k in the
end of the loop (INP or TAMP), the JA-60N will automatically recognize this situation
and from this moment it will react to any change of the resistance (changes ±30% or
more will trigger the input).
Note: if either the INP or TAMP terminal is not used, it must be connected to the GND
terminal. The procedure to enroll the JA-60N with external sensors is identical as de-
scribed in section 4.1. If you change the DIP switch’s setting, the system will accept
the new setting after the detector’s cover is closed.
Fig.15
Fig.16
8. Control panel programming
Functions of the system can be customized. The most convenient programming method is via a connected PC using the
Comlink software (see 14). Programming can also be performed by entering programming sequences from the system
keypad while in the programming mode:
•
Enter the programming mode (entering
F 0 SC
- SC = Service Code, factory default SC=6060), indicated by a „P“ on
the display. This can only be done while the panel is disarmed. In this mode no alarm can be triggered. Detectors and
other accessories can be enrolled, the system parameters can be set up and the system can be tested.
•
The parameters of the control panel can be set by entering programming sequences from the keypad. Any unfinished
programming sequence can be terminated by pressing the
N
key.
•
To exit the programming mode, press the N
key („P“ will turn off). If any fault is indicated when you try to exit the
programming mode, the control panel will inform you about the problem (see programming sequence 39x for more de-
tails).
Alarm system JA-60 "COMFORT"
- 11 -
MDY51319
Summary of Contents for JA-60 "Comfort"
Page 1: ...JA 60 COMFORT Alarm system Installation manual...
Page 2: ......