Goodrive200L
inverters Function parameters
87
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Frequency-decrea
sing point at
sudden power loss
260V
460V
800V
Note:
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during the
switching of the grid.
2. Prohibition of input phase protection can
enable this function.
P11.03
Overvoltage
stall
protection
0:Disable
1:Enable
1
○
P11.04
Protection
voltage at
overvoltage
stall
120~150%(standard bus voltage) (380V)
140%
○
120~150%(standard bus voltage) (220V)
120%
P11.05
Current limit
action
selection
The actual increasing ratio is less than the ratio
of output frequency because of the big load
during ACC running. It is necessary to take
measures to avoid overcurrent fault and the
inverter trips.
During the running of the inverter, this function
will detect the output current and compare it with
the limit defined in P11.06. If it exceeds the level,
the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during
the constant running. If it exceeds the level
continuously, the output frequency will keep on
decreasing to the lower limit. If the output current
is detected to be lower than the limit level, the
inverter will accelerate to run.
01
◎
P11.06
Automatic
current limit
G:
160.0%
◎
P:
120.0%
P11.07
The
decreasing
ratio during
current limit
10.00
Hz/s
◎