Goodrive200L
inverters Fault tracking
128
Fault
code
Fault type
Possible cause
What to do
tE
Autotuning fault
The motor capacity
does not comply with
the inverter capability
The rated parameter
of the motor does not
set correctly.
The offset between
the parameters
autotunting and the
standard parameter is
huge
Autotune overtime
Change the inverter
mode
Set the rated
parameter according to
the motor name plate
Empty the motor load
and reindentify
Check the motor
connection and set the
parameter.
Check if the upper limit
frequency is above 2/3
of the rated frequency.
EEP
EEPROM fault
Error of controlling the
write and read of the
parameters
Damage to EEPROM
Press STOP/RST to
reset
Change the main
control panel
PIDE
PID feedback fault
PID feedback offline
PID feedback source
disappear
Check the PID
feedback signal
Check the PID
feedback source
bCE
Braking unit fault
Braking circuit fault or
damage to the braking
pipes
The external braking
resistor is not
sufficient
Check the braking unit
and change new
braking pipe
Increase the braking
resistor
END
Time reach of factory
setting
The actual running
time of the inverter is
above the internal
setting running time
Ask for the supplier
and adjust the setting
running time