![INVT GD200L-004G-4 Operation Manual Download Page 118](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737118.webp)
Goodrive200L
inverters Basic operation instruction
113
Function
code
Name
Description
Setting
Range
Modify
Factory
setting
P01.17
Feedback
speed
detection
form
0.00~100.00 s(Only P01.16=1
is valid)
0.00~1
00.00
○
0.5s
P01.18
Power on
and
terminal of
running
protect
function
selection
0:Power on and terminal of
running protect is invalid.
1:Power on and terminal of
running protect is valid.
0~1
○
1
P01.25
0Hz
output
selection
0:without voltage output
1:Voltage output
2:The output current of DC
braking is in accordance to
stopping.
0~2
○
1
By setting P01.00=1, the DC braking function is valid.
4.
Close loop vector control
Function
code
Name
Description
Setting
Range
Factory
setting
Modify
P20.00
Encoder type
0:incremental encoder
1:others
0~4
0
●
P20.01
Encoder
pulse number
0~60000
0~6000
0
1024
◎
P20.02
Encoder
direction
0:forward direction
1:reverse direction
0~0x11
1
0
◎
P20.03
Encoder wire
break
detection
time
0.0~10.0s
0~100
1.0s
○
P20.04
Encoder
direction
detection
time
0.0~100.0s
0~1000
0.8s
○