C.6 Reactors
If the distance between the inverter and the motor is longer than 50m, frequent overcurrent
protection may occur to the inverter because of high leakage current caused by parasitic
capacitance effects from the long cables to the ground. In order to avoid the damage of the
motor insulation, it is necessary to add reactor compensation.
The power of the inverter
Input reactor
DC reactor
Output reactor
GD200L -0R7G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD200L -1R5G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD200L -2R2G-4
ACL2-2R2-4
/
OCL2-2R2-4
GD200L -004G/5R5P-4
ACL2-004-4
/
OCL2-004-4
GD200L -5R5G/7R5P-4
ACL2-5R5-4
/
OCL2-5R5-4
GD200L -7R5G/011P-4
ACL2-7R5-4
/
OCL2-7R5-4
GD200L -011G/015P-4
ACL2-011-4
/
OCL2-011-4
GD200L -015G/018P-4
ACL2-015-4
/
OCL2-015-4
GD200L -018G/022P-4
ACL2-018-4
/
OCL2-018-4
GD200L -022G/030P-4
ACL2-022-4
/
OCL2-022-4
GD200L -030G/037P-4
ACL2-030-4
/
OCL2-030-4
GD200L -037G/045P-4
ACL2-037-4
DCL2-037-4
OCL2-037-4
GD200L -045G/055P-4
ACL2-045-4
DCL2-045-4
OCL2-045-4
GD200L -055G/075P-4
ACL2-055-4
DCL2-055-4
OCL2-055-4
GD200L -075G/090P-4
ACL2-075-4
DCL2-075-4
OCL2-075-4
GD200L -090G/110P-4
ACL2-090-4
DCL2-090-4
OCL2-090-4
GD200L -110G/132P-4
ACL2-110-4
DCL2-110-4
OCL2-110-4
GD200L -132G/160P-4
ACL2-132-4
DCL2-132-4
OCL2-132-4
GD200L -160G/185P-4
ACL2-160-4
DCL2-160-4
OCL2-160-4
GD200L -185G/200P-4
ACL2-200-4
DCL2-200-4
OCL2-200-4
GD200L -200G/220P-4
ACL2-200-4
DCL2-200-4
OCL2-200-4
GD200L -220G/250P-4
ACL2-250-4
DCL2-250-4
OCL2-250-4
GD200L -250G/280P-4
ACL2-250-4
DCL2-250-4
OCL2-250-4
GD200L -280G/315P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
GD200L -315G/350P-4
ACL2-315-4
DCL2-315-4
OCL2-315-4
GD200L -350G/400P-4
Standard
DCL2-350-4
OCL2-350-4
GD200L -400G-4
Standard
DCL2-400-4
OCL2-400-4
GD200L -500G-4
Standard
DCL2-500-4
OCL2-500-4
Note:
1.
The rated derate voltage of the input reactor is 2%±15%.
2.
The power factor of the input side is above 90% after adding DC reactor.
3.
The rated derate voltage of the output reactor is 1%±15%.
4.
Above options are external, the customer should indicate when purchasing.