Goodrive200L
inverters Appendix C
174
or more.
It is necessary to add fuse for the avoidance of overload.
It is appropriate to use a breaker (MCCB) which complies with the inverter power in the
3-phase AC power and input power and terminals (R, S and T). The capacity of the inverter
should be 1.5-2 times of the rated current.
Due to the inherent operating principle and construction of circuit
breakers, independent of the manufacturer, hot ionized gases may
escape from the breaker enclosure in case of a short-circuit. To ensure
safe use, special attention must be paid to the installation and
placement of the breakers. Follow the manufacturer’s instructions.
Inverter
Breaker (A)
Fuse (A)
Rated current of the
reactor (A)
GD200-0R7G-4
10
16
12
GD200-1R5G-4
10
16
12
GD200-2R2G-4
16
16
12
GD200-004G/5R5P-4
16
25
12
GD200-5R5G/7R5P-4
25
32
25
GD200-7R5G/011P-4
40
40
25
GD200-011G/015P-4
50
50
40
GD200-015G/018P-4
63
63
40
GD200-018G/022P-4
63
80
50
GD200-022G/030P-4
80
100
65
GD200-030G/037P-4
100
125
80
GD200-037G/045P-4
125
160
95
GD200-045G/055P-4
160
160
115
GD200-055G/075P-4
160
200
150
GD200-075G/090P-4
250
250
185
GD200-090G/110P-4
250
315
225
GD200-110G/132P-4
315
315
265
GD200-132G/160P-4
350
400
330
GD200-160G/185P-4
400
500
400
GD200-185G/200P-4
500
630
500
GD200-200G/220P-4
500
630
500
GD200-220G/250P-4
630
630
500
GD200-250G/280P-4
630
800
630
GD200-280G/315P-4
700
800
630
GD200-315G/350P-4
800
1000
780
GD200-350G/400P-4
800
1000
780
GD200-400G-4
1000
1250
780
GD200-500G-4
1200
1250
980