Goodrive200L
inverters Function parameters
61
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
switching-on
delay time
The setting range :0.000~50.000s
Note:
P06.08 and P06.09 are valid only when
P06.00=1.
P06.09
HDO
switching-off
delay time
0.000s
○
P06.10
RO1
switching-on
delay time
0.000s
○
P06.11
RO1
switching-off
delay time
0.000s
○
P06.12
RO2
switching-on
delay time
0.000s
○
P06.13
RO2
switching-off
delay time
0.000s
○
P06.14 AO1 output 0:Running frequency
1:Setting frequency
2:Ramp reference frequency
3:Running rotation speed
4:Output current
(relative to the rated current of the inverter)
5:Output current
(relative to the rated current of the motor)
6:Output voltage
7:Output power
9:Output torque
10:Analog AI1 input value (The inverter(
≤
15kW)
can be set by the analog potentiometer on the
keypad and AI1 setting is not available for the
device which is 18.5kW or higer than 18.5 kW)
11:Analog AI2 input value
12:Analog AI3 input value
13:High speed pulse HDI input value
14:MODBUS communication set value 1
15:MODBUS communication set value 2
22: Torque current
(relative to the rated current of the motor)
23: Ramp reference frequency(with sign)
0
○
P06.15 AO2 output
0
○
P06.16
HDO
high-speed
pulse output
selection
0
○