Goodrive200L
inverters Basic operation instruction
121
Function
code
Name
Description
Range
Modify
Factory
setting
P03.03
ASR speed
proportion gain
2
0~200.0
0~200.0
○
20.0
P03.04
ASR speed
integral time 2
0.000~10.000s
0.000~10.000
○
0.200s
P03.05
Switch high
point frequency
P03.02~P00.03(Max
frequency)
P03.02~P00.03
○
10.00Hz
P03.09
ACR
proportional
gain P
0~65535
0~65535
○
1000
P03.10
ACR integral
gain I
0~65535
0~65535
○
1000
1.
Elevator accompany with vibration when starting.
Analysis: Motor parameter is inaccuracy, PI parameter set wrongly and the balance
coefficient is bad.
Solution: 1) Redo the motor parameter autotuning, and generally the rotation autotuning is
better than static autotuning.
2) properly modify the parameter of ACR(P03.09,P03.10)and ASR (P03.00)
2.
Elevator accompany with vibration when stopping.
Analysis: the frequency of closed-brake set wrongly.
Solution: properly modify FDT1 lag detection value
3.
Vibration at low speed
Properly modify the value of P03.00 and P03.01.
4.
Vibration at fast speed with
Properly modify the value of P03.03 and P03.04.
10.
Adjust for comfort of start and stop
The function code which can improve the elevator comfort of starting is showed as follow:
P01.01: The start frequency of direct start running;
P01.02: The start frequency holding time;
P01.06: The start time of S-curve acceleration setting;
P01.07: The arrival time of S-curve acceleration setting;
P00.11: Acceleration time;
P03.00: ASR speed proportion gain 1
P03.00: ASR speed integral time 1