![INVT GD200L-004G-4 Operation Manual Download Page 73](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737073.webp)
Goodrive200L
inverters Function parameters
68
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P07.28
Previous fault
type
14:Output side phase loss(SPO)
15:Overheat of the rectifier module(OH1)
16:Overheat fault of the inverter module(OH2)
17:External fault(EF)
18:485 communication fault(CE)
19:Current detection fault(ItE)
20:Motor antotune fault(tE)
21:EEPROM operation fault(EEP)
22:PID response offline fault(PIDE)
23:Braking unit fault(bCE)
24:Running time arrival(END)
25:Electrical overload(OL3)
26:Panel communication fault(PCE)
27:Parameter uploading fault (UPE)
28:Parameter downloading fault(DNE)
32:Grounding short circuit fault 1(ETH1)
33:Grounding short circuit fault 2(ETH2)
36: Undervoltage fault(LL)
●
P07.29
Previous 2
fault type
●
P07.30
Previous 3
fault type
●
P07.31
Previous 4
fault type
●
P07.32
Previous 5
fault type
●
P07.33
Running
frequency at
current fault
0.00Hz
●
P07.34
Ramp
reference
frequency at
current fault
0.00Hz
P07.35
Output
voltage at the
current fault
0V
P07.36
Output
current at
current fault
0.0A
P07.37
Bus voltage
at current
fault
0.0V
P07.38
The Max.
temperature
at current
fault
0.0
℃