Goodrive200L
inverters Function parameters
37
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
before
starting
speed up after the DC braking time. If the DC
braking time is set to 0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated
current of the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
P01.04
The braking
time before
starting
0.00s
◎
P01.05
Acceleration/
deceleration
form
selection
The changing mode of the frequency during
start-up and running.
0: linear type: the output frequency is in
accordance with linear to change.
1:S-curve type: the output frequency is in
accordance with S-curve to change.
S-curve generally applies to the high requirement
position that the starting and stopping should be
.
1
◎
P01.06
The start
time of
S-curve
acceleration
setting
0.0~50.0s
1.5s
○
P01.07
The arrival
time of
S-curve
acceleration
1.5s
○
Output frequency
T
fmax
t1
t2