Goodrive200L
inverters Function parameters
53
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.09
HDI terminal
function
selection
22:ACC/DEC time option 2
23:Simple PLC stop reset
24:Simple PLC pause
25:PID control pause
26:Traverse Pause(stop at the current frequency)
27:Traverse reset(return to the center frequency)
28:Counter reset
29:Torque control prohibition
30:ACC/DEC prohibition
31:Counter trigger
32:Length reset
33:Cancel the frequency change setting
temporarily
34:DC brake
36:Shift the command to the keypad
37:Shift the command to the terminals
38:Shift the command to the communication
39: Pre-exciting command
40:Clear the power
41:Keep the power
42: Contactor feedback signal
43: Braker feedback signal
44: Emergency running enable
61: PID pole switching
0
◎
P05.10
Polarity
selection of
the input
terminals
The function code is used to set the polarity of
the input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
BIT5
BIT6
BIT7
BIT8
S6
S7
S8
HDI
The setting range:0x000~0x1FF
0x000
○
P05.11
ON-OFF filter
time
Set the sample filter time of S1~S8 and HDI
terminals. If the interference is strong, increase
the parameter to avoid the disoperation.
0.000~1.000s
0.010s
○
P05.12
Virtual
terminals
setting
0x000~0x1FF(0: Disabled, 1:Enabled )
BIT0:S1
virtual terminal
BIT1:S2
virtual terminal
BIT2:S3
virtual terminal
0x000
◎